Franklin County Cooperative Inspection Program
The 7th Edition of the Massachusetts State Building Code for 1 & 2 family dwellings is exclusively effective as of January 1, 2008. All permit applications received after this date must comply with these new regulations. It is the contractor’s responsibility to have in his/her possession a copy of the current code and ensure that any project complies with its regulations. Copies can be purchased at the State Bookstore at 436 Dwight St. in Springfield or online: www.sec.state.ma.us/. This is a stand-alone code for 1 & 2family structures.
Since the power point presentation given to contractors in October, there have been amendments to the 7th edition. They are summarized below:
7th Edition Amendment Highlights
Topic |
Section |
Requirement |
Emergency escape |
5310.1.2 |
Minimum height 24”, Minimum width 20” |
Means of Egress |
5311.41 |
Exception allows the two separate exit doors to be located on different levels with walk-outs |
Smoke detectors |
5313.1 |
Must be photoelectric or photoelectric/ionization combination |
CO detectors |
5313.4.1 |
Must have standby power(battery back-up in most cases) |
CO placement |
5313.4.3 |
Outside each bedroom and no more than 10ft from bedroom door |
Frost protection |
5403.1.4.1 |
Exception excludes detached garages from requirement |
Span calculator |
5502.3 |
Permits use of AF&PA Maximum Span Calculator(on-line) in place of tables for joists/rafters |
Flue cross-section |
6001.12.1 |
1/10 of fireplace opening |
Snow Loads |
T5301.2(5) |
FCCIP member towns reduced to 50 |
Wind Loads |
T5301.2(4) |
FCCIP member towns reduced to <90 |
Highlight of 7th Edition Changes
Topic |
Section |
Requirement |
Plans to Fire Chief |
5110.7 |
When application includes fire protection systems, set of plans must be left with fire chief |
CSL Presence |
5116.1 |
Required to be present for the installation of foundation, structural frame, energy conservation, fire protection systems, special construction such as chimneys/fire places, fire-separation wall |
Groundwater |
5116.1 |
CSL must report presence of ground water to BO before pouring footings |
Balcony live load |
5301.5 |
Balconies (see definition p.524) 60 lb. |
Deck live load |
5301.5 |
Decks (see definition p.526) 40 lb. |
Deck attachment |
5502.2.1 |
Cannot be achieved by use of toenails or nails subject to withdrawal. If connection cannot be verified during inspection, decks shall be self-supporting |
Exterior walls |
5302.1 |
Within 3ft of property line must be 1 hr. fire rating from both sides |
Bath ventilation |
5303.3 |
½ baths: window or mech.ventilation; Full bath: mech. ventilation required, window not. |
Intake openings |
5303.4 |
Must be 10’. from plumbing and heating vents, chimneys and other contaminants or 2’below |
Min. room area |
5304.1 |
1 habitable room at least 150sft, all others at least 70sft and >or = 7’ in any direction |
Ceiling Height |
5305.1 |
7’ min. in habitable rooms, except that beams at 4’o.c. or more may be 6’-6” 6’8” min for non-habitable basements, except that beams and other obstructions may be 6’4” |
Topic |
Section |
Requirement |
Tempered glass |
5308.4 |
Required if within 60” of landing or bottom step and less than 60” from floor |
Garage ductwork |
5309.1.1 |
Ductwork in an attached garage must be 26 gauge, min, no openings into garage |
Emergency escape |
5310.1 |
Basements with habitable space shall have at least one escape opening & 1 in each bedroom Location: not more than 44”from floor, may be a bulkhead if certain requirements are met |
|
5310.1 |
Minimum size 5.7 sq.ft., except for double hung (3.3 sq.ft.), and grade floor openings (5 sq.ft) |
|
5310.2 |
Window wells that are part of emergency escape must be 3’x3’min with ladders when >44” |
Means of egress |
5311.2.1 |
Attachment of stairs and similar items can’t depend on toenails or nails subject to withdrawal |
Understair protection |
5311.2.2 |
½”sheetrock (min.) on walls and underside of stairs when enclosed and accessible |
Exit doors |
5311.4.2 |
Two doors required: 1 must be 3-0 x6-8 (cannot exit through garage) 2nd door may be a slider or 2-8 (not 2-6) x 6-8 and may exit through garage if garage has 2-8 x 6-8 side hinged dor |
Landings |
5311.4.3 |
Must be at least as wide as door and 36”min in length (direction of travel) |
Open risers |
5311.5.3.3 |
5 ” max opening unless stairway is less than 30”in height |
Heat detectors |
5313.3 |
Required in attached garages and garage under dwelling. Must be interconnected with smokes |
CO detectors |
5313.4 |
Located on each story, outside every bedroom. Must be hardwired with standby power. |
Sprinklers |
5313.5.1 |
Required in dwellings greater than 14,400 sq. ft. |
Foam thermal barrier |
5314.1.2 |
½” gypsum board(min) except in attics and crawlspaces (see 5314.2.3) |
Drainage |
5401.3 |
Grade must have a minimum slope away from house of 6” in 10ft. |
Frost protection |
5403.1.4.1 |
Accessory structures greater than 400sq. ft (except garages) must have frost protection of 4ft. |
Slopes |
5403.1.7.1 |
Foundation clearances from ascending and descending slopes are regulated by this section |
ICF Foundations |
5404.4 |
Architect/engineer stamp, not more than 2 stories above grade, reinforcement requirements |
Girder/header spans |
5502.5(1) |
Important note: most cases require more than 1 jack support on each end. Jacks must be continuous. (see back page) |
Horizontal firestop |
5602.8 |
Firecaulk required every 10ft horizontally in wall cavities |
Wall bracing |
5602.10 |
Important minimum sheathing requirements for corners adjacent to openings. For walls that support roof only with garage door openings may have a 4:1 aspect ratio (an 8ft high wall may have 2ft corner sheathing provided it is blocked and edge nailed 6”o.c. min) |
Rafter span tables |
5802.5.1 |
Fccip towns use 50lb ground snow load. Raised ceilings have adjustment factor Values are the same for ceilings attached to rafters or ceilings not attached to rafters |
Rafter/joist connect |
5802.5.19 |
See table on p.737 for # of nails required |
Pitch<3 in 12 |
5802.3 |
Structural ridge required |
Truss Bracing |
5802.10.3 |
In the absence of specific bracing requirements, trusses must be braced in accordance with Building Component Safety Information (BCSI 1-03) |
Truss connection |
5802.10.5 |
Truss to wall connection must have approved connector |
Attic Access |
5807.1 |
22x30 (min) access required when there is a 30sq.ft. area, at least 30” high (must be in accessible location, not in closet) |
Ice protection |
5905.2.7.1 |
Ice barrier must extend from eave’s edge to 24” inside the exterior wall line of building |
Wind wash barrier |
6106.3.3.1 |
Solid barrier required from top plate to top of insulation in ventilated attics |
Combustion Air |
6701.1.1 |
Must be brought in from outside in spaces less than 50 cu. ft per 1,000 btu/h input. (Translated, a 100,000 btu appliance in a space that has an 8ft ceiling would need a minimum area of 625 sq.ft.) |
Unlined chimneys |
9303.4 |
Where a solid fuel-burning appliance is vented in an existing, unlined chimney, the chimney must be relined |
This page was last updated on 12/29/2008 .